Contact Us For Quotation | Email: 464560351@qq.com | Whatsapp&Wechat:+8618620373879 |
INTRODUCTION
Xtester-ETCR9220B Wireless H/L Voltage Clamp Leakage Current Meter adopts CT technology and mask digital integration technology, the instrument composed of special clamp current meter and high voltage insulation rod, wireless transmit test data,equiped with wireless receiver which can receive the tested data within straight line distance 30M. If not use insulation rod, which can be used as high accuracy low voltage clamp current meter. Xtester-ETCR9220B series H/L Voltage Clamp Leakage Current Meter connect with insulation rod, which can use for high voltage line current measurement of the wire with insulation skin below 60KV or bare wire below 35KV, online current measurements, also with peak hold, data hold and data storage and so on others functions, the special clamp current meter convenient to clamp or withdraw the tested wire operate by push or pull back the insulation rod, save time and convenient. It is widely used in substations, power plants, and industrial and mining enterprises, inspection stations, electrical maintenance departments for current detection and electrical field operations. It also can replace the H/L voltage transformation ratio tester, which can measure the H/L voltage current of the primary circuit and the secondary circuit respectively, and then calculate the H/L voltage transformation ratio. The insulation rod is light, has the characteristics of moisture-proof, high temperature resistance, impact resistance, bending resistance, high insulation, scalable and so on. |
SPECIFICATION
Function | Description |
Function | Measurement of H/L voltage AC leakage current |
Power Supply | DC 6V (LR03×4 alkaline dry batteries) |
Test Mode | Clamp CT, integration method, the instrument can be hung on the line to test, more convenient to operation |
Transmission Mode | 433MH wireless transmission |
Transmission Distance | 30M |
CT Size | φ68mm |
Measurement Range | 0.00mA~60.0A(50/60Hz automatic) |
Resolution | 0.01mA |
Shift | 0.00A~60.0A automatic shift |
Accuracy (23℃±5℃, below RH<80%) | 0.00mA~999mA:±1%±5dgt |
1.00A~60.0A:±1.5%±5dgt | |
Sampling Rate | 2 time/second |
Display Mode | 4-digit LCD display |
LCD Size | Detector: LCD 35mm×21.5mm |
Receiver: LCD 47mm×28.5mm | |
Meter Size | Detector 135mm×218mm×60mm |
Receiver 78mm×165mm×42mm | |
Data Storage | 99 groups ,display the stored array number during storage of basic products; "MEM" symbol indicates during storage of wireless products,“FULL” symbol display indicate that storage full" |
Line Voltage | Below 60kV current test with insulated skin wire; below 35kV bare wire test (operate with insulation rods) |
Data Hold | In general test mode, press HOLD key to hold data, “DH” symbol display. press HOLD Key once again to cancel this function |
Data Access | “MR” symbol indication, can access all storage data |
Overflow Display | Exceed measure range overflow function: “OL A” symbol display |
No Signal Indication | When the receiver has not received transmit signal, dynamic display “no- -”symbol |
Automatic Shut Down | 15 minutes after boot up, the meter shuts down automatically without any operation, to reduce battery consumption |
Batter Voltage | When battery voltage is lower than 4.8V, display low battery voltage symbol “ ”, and remind to replace the battery |
Meter Weight | 3930g( Including insulation rod and battery) |
Working Environment | -10℃~40℃; Below 80%rh |
Store Environment | -10℃~60℃; Below 70%rh |
Interference | avoid 315MHz, 433MHz same-frequency signal interference |
Insulation Rod Dimension | φ32mm,1m×5PCS |
Insulation Strength | Detcetor/Receiver: AC 2kV/rms ( between the out shell screws) |
AC110kV/rms(all 5pcs insulation rod connect, between the two ends) | |
Structure | Anti-Dripping Type II |
Selection Guide
Mode | Description | Range | Resolution | Clamp | Note |
Xtester-ETCR9200 | H/L Voltage Clamp Current Meter | 0mA~1200A | 1mA | Φ68mm | Base type |
Xtester-ETCR9200B | Wireless H/L Voltage Clamp Current Meter | Wireless type | |||
Xtester-ETCR9220 | H/L Clamp Leakage Current Meter | 0.00mA~60.0A | 0.01mA | Φ68mm | Base type |
Xtester-ETCR9220B | Wireless H/L Clamp Leakage Current Meter | Wireless type |
Packing Details
Package | Outer Package | Carton |
Inner Package | Cloth bag | |
Accessory | Detector | 1 PCS |
Antenna | 1 PCS | |
Insulation Rod(1M) | 5 PCS | |
Tool Bag | 1 PCS | |
Manual | 1 PCS | |
Certificate | 1 PCS | |