This is a low-cost CO2 transmitter designed for applications in HVAC, ventilation systems, offices, schools, and other public places. NDIR CO2 sensor inside with Self-Calibration and up to 15 years lifetime. One analog output of 0~10VDC/4~20mA and six LCD lights for six CO2 ranges within six CO2 ranges make it unique. RS485 communication interface has 15KV anti-static protection, and its Modbus RTU can connect any BAS or HVAC systems. |
Features
Real-time detecting CO2 level. NDIR infrared CO2 module inside with four CO2 detection range selectable. CO2 sensor has Self-Calibration Algorithm and 15 years lifetime Wall-mounting Providing one analog output with voltage or current selectable 0~10VDC/4~20mA selectable easily via jumpers Special “L” series with 6 lights indicates CO2 level and makes CO2 level show clearly. Design for HVAC, ventilation systems, offices, or other public places. Modbus RS485 communication interface optional: 15KV antistatic protection, independent address setting CE-Approval |
TECHNICAL SPECIFICATIONS
Gas detected | Carbon Dioxide (CO2) |
Sensing element | Non-Dispersive Infrared Detector (NDIR) |
Accuracy@25℃(77℉),2000ppm | ±40ppm + 3% of reading or ±75ppm (whichever is greater) |
Stability | <2% of FS over life of sensor (15 yr typical) |
Calibration interval | ABC Logic Self Calibration System |
Response time | <2 minutes for 90% step change |
Warm up time | 2 hours (first time)/2 minutes (operation) |
CO2 measuring range | 0~2,000ppm / 0~5,000ppm selectable in orders 0~20,000ppm / 0~50,000ppm just for TSM-CO2-S series |
Sensor life | Up to 15 years |
Power supply | 24VAC/24VDC |
Consumption | 1.5 W max. ; 0.8 W avg. |
Analog outputs | 0~10VAC or 4~20mA selectable by jumpers |
Relay output | 1X2A switch loadFour set points selectable by jumpers |
6 LED lights(just for TSM-CO2-L series) From left to right:Green/Green/Yellow/Yellow/Red/Red | 1st green light on as CO2 measurement≤600ppm, 1st and 2nd green lights on as CO2 measurement>600ppm and≤800ppm, 1st yellow light on as CO2 measurement>800ppm and≤1,200ppm, 1st and 2nd yellow lights on as CO2 measurement>1,200ppm and≤1,400ppm, 1st red light on as CO2 measurement>1,400ppm and≤1,600ppm, 1st and 2nd red lights on as CO2 measurement>1,600ppm. |
Modbus interface | Modbus RS485 interface9600/14400/19200(default)/28800 or 38400bps (programmable selection), 15KV antistatic protection. |
Operation conditions | 0~50℃(32~122℉); 0~95%RH, non condensing |
Storage conditions | 0~50℃(32~122℉) |
Net weight | 180g |
Dimensions | 100mm×80mm×28mm |
Installation standard | 65mm×65mm or 2”×4”wire box |
Approval | CE-Approval |