China Testing Instruments Manufacturer,Whatsapp/Wechat:+8618620373879  Email: 464560351@qq.com

Xtester-DRKH5-(600-5000A) (AC/DC) 42-100mm Detachable Hall current sensor

Xtester-DRKH5-(600-5000A) (AC/DC) 42-100mm Detachable Hall current sensor

2022-11-24 18:18:42  

Electricity Testing Instruments manufacturer, Support OEM/ODM, your testing specialist

  • Main Features : Xtester-DRKH5-(600-5000A) (AC/DC) 42-100mm Detachable Hall current sensor
  • Serial No. :
Contact Us for QuotationEmail:464560351@qq.comWhatsapp: +8618620373879

Xtester-DRKH5-(600-5000A) (AC/DC) 42*100mm Detachable Hall current sensor

The current sensor based on the Hall Effect open-loop principle can measure DC, AC, pulse and various kinds of Irregular waveform current under electrical isolation conditions.

TECHNICIAL SPECIFICATION

Click to download:Xtester-DRKH5-(600-5000A) (AC/DC) 42*100mm Detachable Hall current sensor Specification

Model Number

          Xtester-DRKH5-(600-5000A)(AC/DC)

Jaw Size

80mm

Rated input Current (IPN)

600

1000

2000

3000

5000

A

Primary Current Measure range(IP)

0~±1200

0~±2000

0~±4000

0~±6000

0~±7500

A

Rated output voltage of secondary side

4±1%

V

Power Supply Voltage (VCC)

DC  ±12V- ±15V  (±5%)

V

Current consumption

VCC=+15V                                      25

mA

Galvanic isolation (Vd)

6KV /50Hz/1min


Linearity (εL)

<1

%FS

Offset Voltage V0

TA =25                                    ±25

mV

Hysteresis offset Current VOM

IPN0                        <±30

mV

Offset Voltage drift VOT

IP=0  TA =-25+85            <±1

mV /

Response time Tr

<7

μs

Operating temperature TA

-25+85

Storage temperature TS

-40+100

Frequency bandwidth(-3dB)

DC-20

KHZ

Load resistance RL

10k

Ω

Matters needing attention:

  • The wrong connection may cause sensor damage. After the sensor is energized, the same phase voltage is measured at the output when the current wire cross the sensor center according the direction arrow indicating label.

  • The output range of the sensor can be adjusted according to the user's needs.

  • During the installation process, before closing the jaw, make sure the connecting interface is aligned, not forcibly closed


Telephone
Email
Map
QQ Chat