China Testing Instruments Manufacturer,Whatsapp/Wechat:+8618620373879  Email: 464560351@qq.com

Xtester-HF8009M 10KV Dielectric loss tester,capacitance dissipation factor tester,Transformer Capacitance&Tan Delta Dissipation Factor Tester

Xtester-HF8009M 10KV Dielectric loss tester,capacitance dissipation factor tester,Transformer Capacitance&Tan Delta Dissipation Factor Tester

2022-12-09 20:49:14  

Dielectric loss tester

  • Main Features :
  • Serial No. :
Contact Us for QuotationEmail:464560351@qq.comWhatsapp: +8618620373879

INTRODUCTION

Automatic anti-interference precision medium loss measuring instrument is used for field anti-interference dielectric loss measurement, or laboratory precision dielectric loss measurement. The instrument is integrated structure, built-in dielectric loss bridge, frequency conversion power supply, test transformer and standard capacitor. Frequency conversion anti-interference and Fourier transform digital filtering technology are used to measure automatically and intelligently. The measured data are very stable under strong interference. The measurement results are displayed by large screen liquid crystal and can be printed out with a micro printer.

TECHNICAL SPECIFICATION

Accuracy

Cx:        ±(reading×1%+1pF)

tgδ

±(reading×1%+0.00040)

Anti-interference

Variable frequency anti-interference

Capacitance range

Internal HV:      3pF~60000pF/12kV        60pF~1μF/0.5Kv

External HV: 3pF~1.5μF/10kV        60pF~30μF/0.5kV

Resolution: Maximum 0.001pF, 4 valid figures.

tgδ range(Tan delta range)

Unlimited, 0.001% resolution, automatic identification for capacitance, inductance and resistance of three tested articles.

Test current range

10μA~5A

Internal HV

Set voltage range: 0.5~12kV

Maximum output current: 200mA

Buck-bust method: continuous stepless regulation

Test frequency: integer frequency of 45~65Hz

49/51Hz,45/55Hz automatic dual variable frequency

Frequency accuracy: ±0.01Hz

External High Voltage

the maximum test current is 5A / 40~70Hz in the forward connection

The maximum test current during reverse wiring is 10kV / 5A / 40~70Hz

CVT self-exciting low voltage output

Output voltage 3~50V,

output current 3~30A

Measuring duration

About 30s, depending on measuring method

Input power supply

180V~270VAC, 50Hz±1%

Computer interface

Standard RS232 interface

Printer

mini-type thermal printer

Environment temperature

-10℃~50℃

Relative humidity

<90%,no condensation

Overall dimension

460×360×350mm

Weight

10kg

Note:

On-site transformer housing is generally grounded. When testing the tgδ(dielectric loss) of transformer, the reverse connection method is generally selected. Only for fully insulated transformer, the forward connection method is used to test.

1F=1000mF=1000000000uF=1000000000000pF

1mF=100001F=1000uF=1000000000000pF

1uF=1000000000000pF

1uF=0.000001F


Telephone
Email
Map
QQ Chat