China Testing Instruments Manufacturer,Whatsapp/Wechat:+8618620373879  Email: 464560351@qq.com

Musktool- SKIM600M Insulation Monitoring Device for IT system

Musktool- SKIM600M Insulation Monitoring Device for IT system

2024-11-28 13:29:16  

SKIM600M Insulation Monitoring Device for IT system

  • Main Features :
  • Serial No. : Zoe553
Contact Us For QuotationEmail:  464560351@qq.comWhatsapp&Wechat:+8618620373879

Musktool- SKIM600M Insulation Monitoring Device for IT system

 

SKIM600M is an insulation monitoring device for IT system main circuits and control circuits below AC690V and DC400V. SKIM600M can only perform insulation monitoring independently (the wiring method can only be used at the AC end) and cannot be combined with the insulation fault location.


Insulation Monitoring Device for IT system

Model*

SKIM200

SKIM400

SKIM600M

SKIM600FL

SKIM600H

Main circuits

X

Control circuits

DC

-

400V

400V

400V

-

AC

230V

400V

690V

690V

1140V

DC/AC

230V

400V/400V

400V/690V

400V/690V

1140V

IFL system

X

X

X

X


SKIM600M Feature:

1. Applicable to IT systems main circuits and control circuits systems below AC690 and DC 400V;
2. Internal/external testing/reset buttons;
3. Automatic and manual reset functions;
4. Multi type, wide range control power input;
5. Humanized and easy to operate interface, which can display various parameters and system leakage capacitance;
6. DIN rail installation method;
7. LCD screen display with backlight;
8. Measure and display the insulation resistance of ungrounded systems;
9. Measurement and display of leakage capacitance (C);
10. Communication via Modbus RS-485;
11. Adjustable response delay;
12. Two independent alarm relays (each relay has a switching contact);
13. N/O or N/C operation (optional).


SKIM600M Technical Data

Item

Value

IT system Rated Voltage

AV690V, DC400V

Rated Power

4kW

Alarm Value Ran 1

1 ~9999 kΩ

Alarm Value Ran 2

1 ~9999 kΩ

Response time at R=0.5xRan and G=1 μ F

4s

Insulation Alarm Delay

09999s

Measure Voltage(U1)

60V

Internal Resistance (R1)

152 kΩ

Measurement Accuracy(1~5 kΩ)

1 kΩ

Measurement Accuracy(5 kΩ~1MΩ)

+15 %

Permissible Leakage Capacitance (Ce)

≤ 200 μF

Positioning Voltage

90V

Positioning Current

<4.5mA

Response time (Fault Location)

<30s

SKIFL12 Accessible quantity

16

 

 



Telephone
Email
Map
QQ Chat