Contact Us For Quotation | Email: 464560351@qq.com | Whatsapp&Wechat:+8618620373879 |
Xtester- SKIM400 Insulation Monitoring Device below AC400V
SKIM400 is an insulation monitoring device for IT system main circuits and control circuits below AC, DC and AC/DC 400V. SKIM400 can only perform insulation monitoring independently and cannot be combined with the insulation fault location. |
Insulation Monitoring Device for IT system
Model* | SKIM200 | SKIM400 | SKIM600M | SKIM600FL | SKIM600H |
Main circuits | X | √ | √ | √ | √ |
Control circuits | √ | √ | √ | √ | √ |
DC | - | 400V | 400V | 400V | - |
AC | 230V | 400V | 690V | 690V | 1140V |
DC/AC | 230V | 400V/400V | 400V/690V | 400V/690V | 1140V |
IFL system | X | X | X | √ | X |
SKIM400 Features:
1. Applicable to IT systems main circuits and control circuits below AC/DC 400V 2. Internal/external testing/reset buttons 3. Automatic and manual reset functions 4. Multi type, wide range control power input 5. Humanized and easy to operate interface, which can display various parameters and system leakage capacitance 6. DIN rail installation method 7. LCD screen display with backlight 8. Measure and display the insulation resistance of ungrounded systems 9. Measurement and display of leakage capacitance (C) 10. Communication via Modbus RS-485 11. Adjustable response delay 12. Two independent alarm relays (each relay has a switching contact) 13. N/O or N/C operation (optional) |
SKIM400 Specification
Item | Value |
IT system Rated Voltage | ≤230V |
Power supply | AC 85-265V, DC18-36V |
Alarm Value Ran 1 | 1…9999 kΩ |
Response time at R=0.5xRan and G=1 μ F | ≤4s |
Insulation Alarm Delay | 0…9999s |
Measure Voltage(U1) | 50V |
Internal Resistance (R1) | ≥152 kΩ |
Resistance Measurement Range | 1kΩ~20MΩ |
Resistance Measurement Range | 1kΩ~20MΩ |
Measurement Accuracy(1~5 kΩ) | 1 kΩ |
Measurement Accuracy(5 kΩ~1MΩ) | +15 % |
+15 %Permissible Leakage Capacitance (Ce) | ≤ 200 μF(Distributed capacitance curve in the manual) |