Xtester-Megger MIT1525 Insulation Resistance Tester, 15kV Industrial Insulation Tester
INTRODUCTION
| Ideal for original equipment manufacturers and industrial companies, this tester features a full suite of test modes, onboard memory, and the ability to stream data/download data to a PC/laptop. Offers rapid charge batteries and operation from an ac source if the ba Features * Includes all test modes * Ramp test plus advanced memory functions with recall to screen * RTC for time/dat stamp of results and USB cable interface to PC/PowerDB * Insulation resistance up to 30 TΩ at 15 kV * IR, Timed IR, DAR, PI, DD, SV and ramp diagnostic tests * High current - 3 mA short circuit current * High noise immunity - 6 mA (15 kV) of noise rejection * Li-ion battery – up to 6 hours continuous testing at 5 kV with a 100 M load, battery meets IEC 2133 * Safety rating: CAT IV 1000 V to 9842.52' (3000 m) - 15 kV * Large LCD display with backlight * Dedicated voltmeter function (30 to 660 V) * Advanced memory, on screen recall and real time clock for date/time stamped results * Download of on-board results via USB interface * Recorded temperature * PowerDB Lite asset management software supplied Applications * Cables * Transformers * Motors * Generators * Circuit breakers * Bushingstteries are dead.  | 
TECHNICAL SPECIFICATION
AC Voltage (Auto-ranging)  | 90 to 264 Vrms, 47 to 63 Hz, 200 VA  | 
Test Voltage  | Range: 1000 V, 2500 V, 5000 V, 10000 V, 15000 V, user defined test voltage Accuracy: +4%, -0%, ±10 V nominal test voltage at 1 GΩ load (0 to 30°C) User defined test voltage: 100 V to 1 kV in 10 steps, 1 to 5 kV in 25 V steps, 5 to 15 kV in 25 V step  | 
Resistance Range  | 10 kΩ to 15 TΩ at 5 kV 10 kΩ to 20 TΩ at 10 kV 10 kΩ to 30 TΩ at 15 kV  | 
Accuracy (68°F [20ºC])  | ±5% from 1 MΩ to 3 TΩ: 15 kV ±5% from 1 MΩ to 2 TΩ: 10 kV ±5% from 1 MΩ to 1 TΩ: 5000 V ±5% from 1 MΩ to 500 GΩ: 2500 V ±5% from 1 MΩ to 200 GΩ: 1000 V ±20% from 1 MΩ to 30 TΩ: 15 kV ±20% from 1 MΩ to 20 TΩ: 10 kV ±20% from 1 MΩ to 10 TΩ: 5000 V ±20% from 1 MΩ to 5 TΩ: 2500 V ±20% from 1 MΩ to 2 TΩ: 1000 V  | 
Guard Terminal Performance  | Guards out parallel leakage resistance down to 250 kΩ with a maximum additional resistance error of 1% with a 100 MΩ load  | 
Short Circuit/Charge Current  | 3 mA at 5 kV, 10 kV, 15 kV  | 
Insulation Test Alarm  | 100 kΩ to 10 GΩ  | 
Capacitor  | Charge: <7.5 s/μF at 3 mA to 15 kV Discharge: <3500 ms/μF to discharge from 15 kV to 50 V  | 
Capacitance  | Range: 10 nF to 50 μF (with test voltage set above 500 V) Measurement accuracy: ±10% ±5 nF  | 
Current  | Range: 0.01 nA to 6 mA Accuracy: ±5% ±0.2 nA at all voltages (20°C)  | 
Interference  | 6 mA from 2100 V to 15 kV  | 
Voltmeter  | Range: 30 V to 660 V AC or DC, 45 to 65 Hz Accuracy: ±3%, ±3 V  | 
Timer Range  | Up to 99 minutes 59 seconds, 15 second minimum setting  | 
Memory Capacity  | 5.5 hours logging at 5 sec intervals  | 
Test Modes  | IR, IR(t), DAR, PI, SV, DD, Ramp test  | 
Interface  | USB type B (device)  | 
Real Time Output  | 1 Hz output readings (V, I, R)  | 
Display Analog  | 100 kΩ to 10 TΩ  | 
Digital  | ![]() 10 kΩ to maximum above  | 
Temperature  | Operating: -4 to 122°F (-20 to 50°C) Storage: -13 to 149°F (-25 to 65°C)  | 
Humidity  | 90% RH non-condensing at 104°F (40°C)  | 
Maximum Altitude  | 9842.52' (3000 m)  | 
IP Rating  | IP65 (lid closed), IP40 (lid open)  | 
Safety  | CAT IV 1000 V to 9842.52' (3000 m) altitude (meets the requirements of IEC 61010-1)  | 
Battery  | Type: 11.1 V, 5.2Ah Li-ion batteries, meets IEC 62133:2003 Life: 4.5 hours (typical) continuous testing at 15 kV with a 100 MΩ load Charge time: 2.5 hours deep discharge, 2 hours normal discharge  | 
Dimensions  | 14.2 x 12 x 7.6" (360 x 305 x 194 mm)  | 
Weight  | 14 lbs (6.5 kg)  | 